Mining and Industrial Boxes |
|
CCG Handi Fit™ Y Box IP66/67/68
for Industrial, Commerical and Mining Electrical Installations
|
 |
Features and Benefits
- Internal earth continuity ring and earth studs provided.
- DIN Rail mounting studs are provided for use with terminal blocks.
- Raised domed lid facilitates connections to be made outside of the box.
- Only approved CCG cable glands and terminals must be used.
- Dust and water tight to IP68 when fitted with CCG sealed cable glands.
- Boxes can be buried for extended periods.
- Boxes with see through polycarbonate “adapt-a-lids” available on request.
- 4-Way H-Boxes with parallel entries available on request.
- Red Fire Rated Box for emergency circuits available (925°C for 3-hours).
Wiring and Installation instructions for IP rated CCG Junction Boxes. - Installation must be carried out by a competent person.
- Do not install under live current conditions.
- The box must not be modified in any way, as this will invalidate the certification.
- All wiring must be carried out in accordance with the relevant Codes of Practice.
- The wiring insulation must not extend by more than 1.0mm from the metal face of the terminal.
- The voltage and current value of the box must not be exceeded.
- See relevant certificate for current limitations for conditions of use / schedule of limitations.
- Only those terminals shown in the terminal schedule may be incorporated in the box.
- Inner cable bedding must protrude into the box by a minimum of 20mm past the cable entry point.
- Not more than one single or multiple strand lead shall be connected into either side of the terminals.
- Only earth conductors of equal size shall be connected with rail mounted terminals.
- All terminal screws used and unused shall be tightened.
- A parallel shaft screw driver of the correct size should be used for rail mounted terminals screws.
- Where cables enter the box they must be secured by CCG Cable Glands appropriate to the make up of the cable.
- Unused entry apertures must be blanked with certified CCG Blanking Plugs.
- To maintain IP66/68 a thread seal gasket between the box and cable gland must be installed.
- Before replacing the lid, ensure the lid gasket is in place.
- The use of a CCG Box Spanner (Lid Locking Key) is required to maintain the tamper proof integrity of the box.
|
|
|
|